MAXS67 218HF 110-254V/50-60Hz TW PC BN25

Explosion proof Ex e lighting fixtures are applicable for hazardous areas, zone 1. They are designed to meet IEC, Ex and maritime requirements and to save maintenance cost due to the long lifetime.

On stock

Product sheet

Vare Nr. 004956

Explosion proof light, in Stainless Steel AISI 316L, for hazardous areas. Classified II 2GD Ex d e mb IIC T4 Gb, and II 2GD Ex tb IIIC T70°C Db for dust. Impact classification IK10, IP66/67. Light source T8. 2x18W. Ballast type HF (High frequency). Through wiring 6×2,5 mm². Cable entry 2xM25-Nickel plated brass. Optic type Clear, with Polycarbonate diffusor.

Technical data
EX gas classification:II 2GD Ex d e mb IIC T4 Gb
EX dust classification:II 2GD Ex tb IIIC T70°C Db
IP classification:66/67
IK Classification:10
Minimum ambient temperature (ºC)-30
Maximum ambient temperature (°C)50
Dimensions
Net weight (kg)4,7
Length (mm)724
Width (mm):165
Height (mm):128
CCmax (mm):704
CCmin (mm):704
Body
Body materialStainless Steel AISI 316L
Colour of body:White
Body colour code:White
Optic
Optic:Clear
Material of diffuser:Polycarbonate
Lightdistribution Up/Down:10/90
Electrical data
Minimum Voltage -10% (V)110
Maximum voltage +10% (V)254
Minimum frequency -5% (Hz)50
Maximum frequency +5% (Hz)60
Minimum voltage in DC220
Maximum voltage in DC250
Total consumption (W)36
Number of fixtures on a MCB10 type B fuse20
Number of fixtures on a MCB10 type C fuse34
Number of fixtures on a MCB16 type B fuse33
Number of fixtures on a MCB16 type C fuse55
Ballast/Driver
Type of ballast/driverHF (High frequency)
Number of ballast/driver1
Light data
Light sourceT8
Lamp baseG13
Number of lamps2
Lamp power (W)18
Termination
Type of cable glandM25-Nickel plated brass
Number of cable glands2
Minimum cable diameter10
Maximum cable diameter18
Termination6x6mm² screw terminal block
Type of blind-plugM25-Nickel plated brass
Number of blind plugs2
Type of through wiring6x2,5